Solution Case for the Electrical Fault in a Bank Computer Center
Cheng Shaoyi(Gansu Institute of Architectural Design & Research,Lanzhou 730030,China)
Feng Zhiwen(Shanxi Architectural Design & Research Institute Co.,Ltd.,Xi’an 710003,China)
Abstract The analysis process and solutions for the electrical fault in a bank computer center are introduced. UPS switch along with the external protection switch tripped many times because of fault,the causes of which are that:① the N conductor and the PE conductor in the TN-C-S system are first separated and then combined;② three-phase load is unbalanced;③ harmonic impact.
Key words Electrical fault Grounding Three-phase load unbalance Voltage between N conductor and ground Neutral point offset Harmonics
摘 要 介绍了某银行计算机中心电气故障的分析过程和解决措施。UPS 保护开关连同外部保护开关多次发生故障跳闸,分析其原因为:① TN - C - S 系统中 N 线与 PE 线分开后又合并;② 三相负荷不平衡;③ 谐波影响。
关键词 电气故障 接地 三相负荷不平衡 N线对地电压 中性点偏移 谐波